0-10 V Lighting Control

0-10 V Lighting Control

0-10 V is one of the earliest and simplest electronic lighting control signaling systems; simply put, the control signal is a DC voltage that varies between zero and ten volts. The controlled lighting should scale its output so that at 10 V, the controlled light should be at 100% of its potential output, and at 0 V it should at 0% output (i.e. “Off”). Dimming devices may be designed to respond in various patterns to the intermediate voltages, giving output curves that are linear for: voltage output, actual light output, power output, or perceived light output.

There are two variations to the 0 to 10 V system, 0 to -10 V and 0 to +10 V. Despite being incompatible with each other, both systems were widely implemented by lighting manufacturers.

Dimming fluorescent ballasts and dimming LED drivers often use 0-10 V control signals to control dimming functions. In many cases, the dimming range of the power supply or ballast is limited. If the light output can only be dimmed from 100% down to 10%, there must be a switch or relay available to kill power to the system and turn the light completely off.

Most 0-10 V controllers offer either a built-in line voltage relay or an external line voltage relay. Depending on the application, these options should be considered.

In production lighting this system was replaced by analog multiplexed systems such as D54 and AMX192, which themselves have been almost completely replaced by DMX512. For dimmable fluorescent lamps (where it operates instead at 1-10 V, where 1 V is minimum and 0 V is off) the system is being replaced by DSI, which itself is in the process of being replaced by DALI.

When using this system, one must take into consideration the actual application, since controlling office lights is not the same as controlling theatrical lighting. 0-10 V lighting control is widely used in commercial and industrial lighting by ballast manufacturers such as GE, Philips, Universal, Metrolight, and Sylvania. There are distributed control approaches on the market today that can be installed inside or very near the fixture(s) to be controlled thus eliminating the wire runs and the voltage drop.

Read more about 0-10 V Lighting Control:  Advantages and Disadvantages

Famous quotes containing the words lighting and/or control:

    No one after lighting a lamp puts it under the bushel basket, but on the lampstand, and it gives light to all in the house. In the same way, let your light shine before others, so that they may see your good works and give glory to your Father in heaven.
    Bible: New Testament, Matthew 5:15,16.

    Not being able to control events, I control myself; and I adapt myself to them, if they do not adapt themselves to me.
    Michel de Montaigne (1533–1592)